Solid insulated ring network cabinet core unit

Five-prevention interlocking design
  1. Avoid opening and closing the isolating switch with load - the isolating operation hole is blocked by the interlocking plate after the circuit breaker is closed
  2. Avoid mis-opening and mis-closing of circuit breaker and high-voltage load switch—after the lower cabinet door is opened, the circuit breaker can not be opened
  3. Prevent live closing of earthing switch—the isolating and earthing operation hole is blocked by interlocking plate after closing of circuit breaker
  4. Prevent power transmission with grounding switch – the interlocking plate after the circuit breaker is closed blocks the grounding operation hole
  5. Prevention of straying into the charged compartment - the door of the cable room can only be opened after the grounding switch is closed first and then the circuit breaker is closed again